 Alexander
Wolf & Company, Inc. is a 50 year old full-service
Real Estate Management firm with offices in Long Island and New York
City. They specialize in the management of Cooperatives, Condominiums,
Home Owners Associations and Senior Housing Communities in the New
York Metropolitan area.
They are a technology-driven, customer-oriented firm with a reputation
for around the clock responsiveness to their customers’ needs.
They are sensitive to the challenges and demands of the community
they serve and are always looking out for the best and most economical
services for the facilities they manage.
The Challenge:
In their quest for operational excellence and maximum cost savings,
Alexander-Wolf contacted Energy Conservation Services Corp. (ECS)
seeking additional savings on their heating oil consumption. ECS
recommended an IntelliCon control and completed a comparative fuel
utilization study based on heating oil bills provided by Amerada-Hess
Corporation.
Facility: Residential, condominiums.
Location: Midtown New Your City, New York.
The Products Used:
IntelliCon-CHS - Commercial Steam Heating System Fuel Economizer
A single IntelliCon-CHS was installed on a 6,300,000 BTU steam boiler
that was providing heat and domestic hot water in the building. The
economizer was installed on December 7, 2005 and was operational
on a 24x7 basis throughout the testing period. The testing period
ran from January 2006 through April 2006.
The Results:
Energy Savings: The IntelliCon control performed
as designed. During the four month study period, the actual number
of gallons of oil consumed dropped from 17,614 to 12,604. Of course,
the winter of 2006 was less severe than in 2005, according to historical
data collected by NOAA (National Oceanic & Atmospheric Administration)
for New York City. By normalizing fuel consumption against the daily
temperatures, the resulting savings amounted to 2,197 gallons of
Number 2 heating oil. As a result, Alexander-Wolf experienced a tangible
savings of 12.12%.
In addition, the IntelliCon controller reduced on/off cycling significantly
thereby extending the operational life for these systems while also
reducing their attendant maintenance costs.
| Customer Unit |
IntelliCon Control |
Measured Reduction in Energy/Fuel Consumption |
| Federal Boiler Model FST-150 |
CHS |
12.12% |
Payback Period: Based on normalized consumption
at an average 2006 cost of $1.67 per gallon of heating oil, they
saved about $3,700. As a result, the ROI period for this Intellidyne
upgrade is a short 4.8 months.
|